In short
Thermostatic mixing valves (TMVs) hold hot water at a safe temperature at basins and showers. They matter most where children, older people or patients use the outlets. Proximity Plumbing tests outlet temperatures, services and replaces TMVs, and records the results for your audits.
HOW IT WORKS
How a TMV works
Hot water is usually stored hotter than is safe at a tap. A thermostatic mixing valve, or TMV, sits between the hot water supply and the outlets it serves and blends hot and cold water to a set temperature. A temperature-sensitive element inside the valve expands and contracts to hold that temperature steady when someone flushes a toilet or turns on another tap.
The most important thing a TMV does is fail safe. If the cold supply drops away, a working valve shuts off the hot water instantly, so nobody is scalded. The thermal shutdown test at every service proves it still does.
NSW Health’s policy for hospitals uses the Public Health Act definitions: a hot water system delivers water of at least 60°C at each outlet, and a warm water system, such as a TMV system, delivers water below 60°C (NSW Health PD2015_008). NSW Health notes that warm water systems, including TMVs, may allow Legionella bacteria to grow (NSW Health), which is why servicing matters as much as temperature.
THE SIGNS
When TMVs need attention
- Hot water too hot or too cold at a basin
- Temperature changes when other taps run
- A service is due
- An audit or inspection is coming
- TMVs that have never been serviced
- New basins or showers fitted
HOW URGENT IS IT?
Is it urgent?
| What you notice | What it usually means | How urgent |
|---|---|---|
| Water at a basin or shower too hot to hold a hand under | The valve has drifted or failed | Emergency. Stop using that outlet and call us. In a hospital or nursing home, isolate the system |
| The temperature swings when another tap or toilet is used | Blocked strainers, or an element that is wearing out | Soon. Book a service |
| Warm water only trickles out | Blocked strainers or check valves, or a flow below the valve’s minimum | Soon. Book a service |
| No record of the last service | The valve may never have been serviced | Plan. Register and test every valve |
WHAT CAUSES IT
Why TMVs drift
Scale and debris build up in the valve and its strainers, and the thermostatic element wears. Over time the outlet temperature drifts from where it was set.
HOW WE DIAGNOSE IT
How we test and service them
We measure the outlet temperature, test that the valve shuts off hot water if the cold supply fails, clean or replace strainers and parts, reset the temperature and record the results.
YOUR OPTIONS
Service, repair or replace
| Option | Best for | Pros | Cons | Disruption |
|---|---|---|---|---|
| Service | Valves within their design life | Restores accurate control; the lowest cost | Parts for older models can be hard to find | Low: outlets off for a short time |
| Replace the element or cartridge | Valves that drift soon after a service | Fixes the part that wears; the valve body stays | Only possible where parts are available | Low |
| Replace the valve | Obsolete or repeatedly failing valves, or valves not approved for a hospital | A new valve with current approvals and a fresh service history | Higher cost | Low to medium |
INSPECTION AND MAINTENANCE
Temperatures and checks in NSW
| Where or what | Requirement | Source |
|---|---|---|
| Aged care, patient care areas, early childhood centres, school areas used by children and disability facilities | Heated water at the outlet no hotter than 45°C | NCC, NSW |
| All other buildings | No hotter than 50°C at the outlet | NCC, NSW |
| Hospital patient areas, adults | 40.5°C to 45.0°C at the outlet, with thermal shut-off at 46.0°C | NSW Health |
| Hospital patient areas, children | 38.0°C to 40.5°C at the outlet, with thermal shut-off at 43.5°C | NSW Health |
| Monthly check in hospitals and nursing homes | At least one outlet served by each TMV, preferably a hand basin, running at 6 to 10 litres a minute: 12 to 20 seconds to fill a 2 litre jug | NSW Health |
| A variation of 2°C or more in a hospital | Isolate the system after a 20 second stabilisation period, and keep it out of use until it is checked and repaired | NSW Health |
| Servicing | To the manufacturer’s instructions and AS 4032, by a licensed plumber | NSW Health |
COMPLIANCE AND STANDARDS
Standards and records
In NSW, heated water at outlets used by children, older people, patients and people with a disability must be no hotter than 45°C (National Construction Code, NSW). In health care facilities, NSW Health requires a monthly temperature check at an outlet served by each TMV, recorded, and servicing by a licensed plumber trained in TMVs (NSW Health PD2015_008). We test, service and record every valve so your records are ready for an audit.
In hospitals, TMVs and warm water systems must also hold WaterMark certification and be on NSW Health’s list of approved systems. Any repair or parts must be written up in a service report that explains the temperature variation, and site management acknowledges the report before the system goes back into use.
WHAT YOU RECEIVE
What goes in your TMV register
- A tag number for each valve, its location and the outlets it serves
- Make, model and installation date, and whether it is an approved valve where a hospital needs one
- The set temperature, and the temperatures we measured at each outlet
- The result of the thermal shutdown test
- Strainers cleaned, parts replaced, and anything still to fix
- The date, the plumber’s name and licence number, and when the valve is next due
PROCESS AND TIMELINE
How a TMV service runs
1
Register
We list every TMV and the outlets it serves.
2
Test
Outlet temperatures and the cold-water failure test.
3
Service
Strainers cleaned, parts replaced, temperature reset.
4
Record
Results recorded for your audit file.
WHAT IT COSTS
What TMV servicing costs
TMV servicing is priced by the number of valves and how easy they are to reach: a valve in an open cupboard takes far less time than one above a ceiling. Replacement valves are quoted separately.
A service kit costs much less than a new valve, so the register earns its keep: valves that need parts at every visit are the ones to budget to replace. TMV testing and records are included in our Compliance and Premium Care Plans.
HOW TO BRIEF US
How to brief us
- The type of facility: hospital, aged care, childcare, school, clinic or office
- How many TMVs you have, if you know, and where they are
- Your existing register or the last service reports
- Which outlets are used most, and when they can be out of use for testing
- Any outlet that has run too hot or too cold recently
QUESTIONS TO ASK
Questions to ask about TMVs
- What service interval applies to our valves, and where does it come from? It should come from the manufacturer’s instructions and AS 4032, in writing.
- Was the thermal shutdown test done on every valve? It is the test that proves the valve fails safe.
- Is the plumber trained in TMVs? NSW Health requires it in hospitals, and it is good practice everywhere.
- Can I keep the register as a document? Auditors and inspectors ask for it.
FROM OUR RECORDS
Valves wear out before heaters do
Across our hot water repair jobs since 2019 where a cause was recorded, a faulty tempering valve was the most common (33 jobs), ahead of faulty elements or thermostats (15) and water leaks (13). A tempering valve is the simpler cousin of a TMV, usually fitted at the heater, but it wears in the same way: scale, debris and a tired element.
QUESTIONS
TMV questions
GUIDES
Guides and next steps
COMMERCIAL & STRATA
Explore Commercial & Strata
Who we help
Services

TMV SERVICING
Get your TMVs tested and recorded
Log a TMV service, or put it on a Compliance Care Plan.
Planning ahead? Request our compliance pack, book a free building health check or invite us to your contractor panel.
Licensed NSW 285594C
24/7 priority response
Report and photos on every job
4.9 from 3,000+ Google reviews