Plant room checklist: weekly, monthly and yearly

A simple weekly, monthly and yearly routine for hot water plant, pumps, valves and backflow devices, with the legal items clearly marked.

24/7 PRIORITY RESPONSE | WORK ORDERS | COMPLIANCE PACK

Google

Overall Rating

4.9

Five stars

(3,000+)

Brightest & Best Business Awards: Winner 2019, Winner 2024, Winner 2025, People's Choice 2025, Finalist 2023

NOW SERVICING NORTH SYDNEY

  • NSW Contractor Licence 285594C
  • 24/7 Priority Response
  • 5,183 Commercial Jobs Since 2019
  • Report and Photos on Every Job
  • Invoices With Your PO and SP Number
  • Onsite in 30 Minutes Guaranteed

KEY TAKEAWAYS

Quick answer

Reviewed by William Demirdonder, licensed plumber, NSW licence 275278C, on 8 November 2026

  • Building managers
  • Facility managers
  • Compliance
  • 6 min read

Quick answer

Weekly, walk the plant room and look and listen: leaks, water on the floor, warning lights, pumps running constantly, smells from pits. Monthly, check valves are labelled and reachable, read the water meter for unexplained use, and do the TMV temperature check if you run a hospital or nursing home. Yearly, book the backflow test, which Sydney Water requires, and the servicing the manufacturers call for.

  • Weekly and monthly checks are looks and listens, not repairs.
  • Testable backflow devices must be tested every year by an accredited plumber.
  • Never enter a pump well or pit: SafeWork NSW treats them as confined spaces.
  • Write everything down. A plant room log is your proof at audit time.

GUIDE

How to use this checklist

This is our suggested routine, not a legal schedule. Manufacturer's instructions, your maintenance contracts and any legal requirement come first. Items with a legal requirement are marked.

Watch out

Pump wells, pits, tanks and sewers can be confined spaces. SafeWork NSW requires a written risk assessment and an entry permit before anyone goes in (SafeWork NSW). Look from outside only.

Split the work by who is allowed to do it. Building staff observe and record. Licensed trades adjust, repair and test.

WhoPlant room tasks
Building or facilities staffWeekly and monthly looks and listens, meter readings, the log, keeping access clear
Licensed plumberHot water plant, valves, pumps and floats, TMV servicing, leak repairs
Accredited backflow plumberThe yearly test of each testable backflow device, and lodging the results
Licensed gasfitterAnything on gas hot water plant or boilers, including burners and flues
Licensed electricianPump control panels, switchboards and alarms wiring
Fire services contractorFire sprinkler and hydrant valves, which nobody else should touch

GUIDE

Weekly: look and listen

  • Leaks or drips under the hot water plant, around valves and at pipe joints.
  • Water on the floor, or around the pump pit.
  • Warning lights or error codes on hot water units and pump control panels.
  • A relief valve drain that keeps running.
  • Pumps that run constantly, cycle on and off, or make a new noise.
  • Smells from pits or floor wastes.
  • Access clear, doors locked, and nothing stored against the plant.

Weekly checks only work if you know what normal looks like. On a day when everything is working, photograph each pressure gauge and control panel display, time how long a sump pump runs and how often it starts, and note the sound the plant makes. Put those notes at the front of the log. A change from normal is what you are looking for, and it is far easier to spot against a baseline.

GUIDE

What should be on the plant room wall

  • A valve map showing which valve feeds which floors, lots or tenancies.
  • The building's plumbing emergency procedure, with phone numbers for your plumber, electrician and fire services contractor.
  • A list of the plant: each hot water unit, pump, backflow device and TMV, with make, model and install date.
  • The plant room log, or where to find it.

When a contractor arrives at 2 am, these four things save more time than anything else.

GUIDE

Monthly

  • Isolation valves labelled and reachable. Don't force a stiff valve: report it.
  • Water meter read and compared with last month. A jump with no reason can mean a hidden leak.
  • Stormwater pits and grates near the plant room clear of silt and leaves.
  • Plant room log up to date, with any faults reported.
  • Legal requirement in hospitals and nursing homes: NSW Health requires a monthly temperature safety check of warm water from at least one outlet, preferably a hand basin, served by each TMV, with the temperature recorded (NSW Health PD2015_008).

Reading the meter for leaks. Sydney Water's leak check for a home is simple: note the numbers on the meter, use no water for at least an hour, then read it again. If the numbers have moved, there is a leak, and the bigger the change, the bigger the leak (Sydney Water: leak detection). An occupied building rarely goes an hour without water, so read the meter at the same quiet hour each month and compare. A steady rise overnight, when almost nobody is using water, is the clue to follow up.

If a licensed plumber finds and repairs a hidden leak, Sydney Water says you can apply for a hidden leak allowance on the bill. Keep the plumber's report for the application.

GUIDE

Yearly

  • Legal requirement: each testable backflow device tested by an accredited backflow plumber, with results sent to Sydney Water within 2 days (Sydney Water).
  • Hot water plant serviced as the manufacturer's instructions require.
  • TMVs serviced as the manufacturer's instructions and AS 4032 require, by a licensed plumber.
  • Pumps, floats and alarms checked by your plumber, with an electrician for the controls where needed.
  • Isolation valves exercised by a plumber, and any that no longer close replaced.
  • Box gutters, roof outlets and stormwater pitscleared before storm season.
  • Asset list, key and access records, and the 10-year capital works plan reviewed.

GUIDE

Keep a plant room log

For every check, write the date, who did it, what they found and what happened next. Add photos. Keep backflow test results, TMV records and service reports in the same place.

In hospitals and nursing homes, NSW Health requires a commissioning or maintenance report form whenever a TMV is commissioned or serviced, and a service report explaining any temperature variation before the system goes back into use.

There is a health reason behind the TMV paperwork. NSW Health notes that warm water systems, including TMVs, may allow the growth and transmission of Legionella bacteria, and that they are regulated under the Public Health Regulation (NSW Health: Legionella control). A log that shows regular servicing and temperature checks is how you show those valves are being managed.

A good log entry is short. A typical example: "12 March, 7.40am, building manager. Hot water unit 2 relief valve dripping into the tundish, about a cup an hour. Reported to plumber, job booked for 14 March." Anyone reading it later knows what happened, when and what was done.

GUIDE

When to call a plumber straight away

  • A pump high-level alarm, or sewage backing up.
  • Water spreading across the floor or through a ceiling.
  • No hot water to part of the building.
  • A smell of gas. Leave the area and follow our gas leak steps.

P1 emergencies are onsite within 30 minutes, 24/7. For the planned items, a Building Care Plan puts pumps, hot water plant, backflow devices, TMVs and stormwater on a schedule, with a report after every visit.

DOWNLOAD

Plant room checklist

Free to download and print: Plant room checklist.

QUESTIONS

Questions

SERVICES

How we can help

SOURCES

Sources

Last updated 8 November 2026. General information, not legal advice.

COMMERCIAL & STRATA

Explore Commercial & Strata

KNOWLEDGE CENTRE

Need a hand with this?

Log a job, or start with a free health check of your building.

Planning ahead? Request our compliance pack, book a free building health check or invite us to your contractor panel.

Licensed NSW 285594C

24/7 priority response

Report and photos on every job

4.9 from 3,000+ Google reviews