TMVs: where they are required and how often to service them
NSW limits hot water to 45°C where children, older people, patients and people with a disability wash. Here is where TMVs fit and how to service them.
24/7 PRIORITY RESPONSE | WORK ORDERS | COMPLIANCE PACK

NOW SERVICING NORTH SYDNEY
WE ARE AVAILABLE
- NSW Contractor Licence 285594C
- 24/7 Priority Response
- 5,183 Commercial Jobs Since 2019
- Report and Photos on Every Job
- Invoices With Your PO and SP Number
- Onsite in 30 Minutes Guaranteed
KEY TAKEAWAYS
Quick answer
Reviewed by William Demirdonder, licensed plumber, NSW licence 275278C, on 8 November 2026
Quick answer
In NSW, hot water at sanitary fixtures must be no hotter than 45°C in aged care residential areas, patient care areas, early childhood centres, school areas used by children and facilities for people with a disability, and no hotter than 50°C elsewhere. A thermostatic mixing valve (TMV) is one common way to hold that. Service TMVs to the manufacturer's instructions and AS 4032. Hospitals and nursing homes also need a monthly recorded temperature check.
- 45°C is the NSW limit at outlets in aged care, patient care, childcare, schools and disability facilities.
- In hospitals and nursing homes, NSW Health requires a monthly recorded temperature check for each TMV.
- Servicing follows the manufacturer's instructions and AS 4032. Ask for the interval in writing.
- Only a licensed plumber should service TMVs, and NSW Health requires TMV training for health care work.
GUIDE
What a TMV does
A thermostatic mixing valve mixes hot and cold water to a set temperature, and keeps it there when pressures change. If the cold supply fails, a working TMV shuts off the hot water so nobody is scalded.
Over time, scale and debris build up in the valve and its strainers, and the thermostatic element wears. The outlet temperature then drifts from where it was set, which is why TMVs need testing and servicing.
GUIDE
Where the 45°C limit applies
The NSW heated water rules in the National Construction Code set these maximum temperatures at the outlet of each sanitary fixture (NCC, NSW variation):
| Where | Maximum at the outlet |
|---|---|
| Residential parts of aged care buildings | 45°C |
| Patient care areas in health care buildings | 45°C |
| Parts of early childhood centres, primary and secondary schools used by children | 45°C |
| Facilities designated for people with a disability | 45°C |
| All other cases | 50°C |
The limit must be achieved in accordance with AS/NZS 3500.4. A TMV is one way to do it. If you are not sure an older installation meets these limits, have the outlet temperatures tested.
These limits come from NCC 2022, which is the edition in force in NSW today. The NSW Government says NSW will adopt NCC 2025 on 1 May 2027 (NSW Government: how to comply with the NCC). If you are planning new hot water work for a care building around that date, ask your plumber which edition the design follows.
The 45°C limit is about the people using the outlet, not the type of business. A medical centre's patient bathroom and a staff kitchenette in the same building can sit under different limits, so map the outlets one by one.
GUIDE
Hospitals and nursing homes: NSW Health rules
NSW Health policy directive PD2015_008 applies to hospitals as defined in the Public Health Act 2010, which includes public hospitals, private health facilities, declared mental health facilities and nursing homes (NSW Health PD2015_008). It requires:
- NSW Health approved warm water systems in all bathing and ablution areas patients can normally reach.
- A monthly temperature safety check from at least one outlet, preferably a hand basin, served by each TMV, with the temperature recorded.
- Immediate isolation of the system if the temperature varies by 2°C or more from the manufacturer's range, until it is checked and repaired.
- A commissioning or maintenance report form whenever a TMV is commissioned or serviced.
- Servicing by a licensed plumber who is trained by a Registered Training Organisation and experienced in TMV maintenance.
- Compliance with AS 4032 and the manufacturer's published instructions.
Scalding is only half the reason. NSW Health notes that warm water systems, including TMVs, may allow the growth and transmission of Legionella bacteria, and are regulated under the Public Health Regulation (NSW Health: Legionella control). Under the Public Health Regulation 2022, a warm water system must not be installed in a hospital unless it is of a kind approved in writing by the Secretary of NSW Health, and the occupier must make sure the local council is notified of an installation or a change in its particulars (NSW Health: warm water systems).
So before replacing a valve in a hospital or nursing home with a different model, check the replacement is an approved kind and that the council notice is handled.
GUIDE
How often to service them
There is no single interval that suits every valve. The servicing schedule comes from the manufacturer's instructions and AS 4032, and it can differ between valve models. Ask your plumber to give you the interval in writing, with the document it comes from.
Outside health care, there is no NSW Health monthly check, but the same logic applies: set a schedule from the manufacturer's instructions, test outlet temperatures, and record every visit. Childcare centres, schools and aged care homes should keep these records ready for inspections.
Watch out
Be wary of anyone who quotes a single servicing interval for every TMV without checking the make and model.
GUIDE
Keep a TMV register
A simple register makes audits and inspections easy. For each valve, record:
- Where it is, its make and model, and the outlets it serves.
- The date of each test or service, and who did it, with their licence number.
- The temperatures measured at the outlets.
- Any parts replaced and any faults found.
- When it is next due.
Keep the register with the building's compliance records, next to the backflow test results.
GUIDE
Signs a TMV needs attention between services
Staff and cleaners use the outlets every day, so they notice problems first. Tell them what to report:
| What staff notice | What it can mean | What to do |
|---|---|---|
| Water at a basin feels hotter than usual | The valve has drifted or failed | Stop using the outlet, put up a sign and call a plumber the same day |
| Temperature swings when another tap or a flush runs nearby | Strainers part-blocked, or a worn thermostatic element | Book a service before the next scheduled visit |
| Weak flow at the outlets one valve serves | Scale or debris in the strainers | Book a service |
| Only cold water at a group of outlets | A hot supply problem, or the valve has shut down as designed | Call a plumber to find out which |
| Dripping from the valve cabinet or access panel | A leaking fitting or valve body | Report it; water near a cabinet can hide a bigger leak |
Write each report in the register, even if the plumber finds nothing. A pattern of small complaints at one valve often comes before a failed test.
GUIDE
What a TMV service includes
- Register: list every TMV and the outlets it serves.
- Test: measure outlet temperatures and run the cold water failure test.
- Service: clean the strainers, replace worn parts and reset the temperature.
- Record: write down the temperatures measured, the work done and who did it.
Ask your plumber
Can I have a register of every TMV in the building, the outlets each one serves, and the date each is next due?
If you need your TMVs tested and recorded, see TMV servicing.
QUESTIONS
Questions
SERVICES
How we can help
SOURCES
Sources
Last updated 8 November 2026. General information, not legal advice.
COMMERCIAL & STRATA
Explore Commercial & Strata
Who we help
Services

KNOWLEDGE CENTRE
Need a hand with this?
Log a job, or start with a free health check of your building.
Planning ahead? Request our compliance pack, book a free building health check or invite us to your contractor panel.