Backflow prevention devices: NSW testing requirements explained

Sydney Water requires testable backflow devices to be tested every year by an accredited plumber. Here is what that means for your building.

24/7 PRIORITY RESPONSE | WORK ORDERS | COMPLIANCE PACK

Google

Overall Rating

4.9

Five stars

(3,000+)

Brightest & Best Business Awards: Winner 2019, Winner 2024, Winner 2025, People's Choice 2025, Finalist 2023

NOW SERVICING NORTH SYDNEY

  • NSW Contractor Licence 285594C
  • 24/7 Priority Response
  • 5,183 Commercial Jobs Since 2019
  • Report and Photos on Every Job
  • Invoices With Your PO and SP Number
  • Onsite in 30 Minutes Guaranteed

KEY TAKEAWAYS

Quick answer

Reviewed by William Demirdonder, licensed plumber, NSW licence 275278C, on 8 November 2026

  • Building managers
  • Facility managers
  • Strata managers
  • Business owners
  • Compliance
  • 7 min read

Quick answer

Backflow devices stop dirty water flowing back into the drinking water supply. In Sydney Water's area, the property owner must have the right device fitted, keep it in good working order, and have testable devices tested every year by an accredited backflow plumber. The plumber sends the results to Sydney Water within 2 days. If you don't comply, Sydney Water can test the device and charge you, restrict the supply or disconnect the property.

  • Testable devices are tested every year, by an accredited backflow plumber only.
  • Results go to Sydney Water within 2 days of the test.
  • The device must match the site's hazard rating. An unknown hazard is treated as high.
  • Sprinkler and hydrant services need a double check detector assembly.

GUIDE

What backflow is

Backflow is water flowing the wrong way: out of a building's plumbing and back into the mains. It can happen when mains pressure drops, for example during a burst main, or when pressure inside the building is higher than the supply. Water from a fire service, a tank or equipment can then be drawn back into the drinking water.

Backflow prevention uses a valve that only lets water go one way, an air gap, or a break tank (Sydney Water).

GUIDE

The owner's duties

  • Have the correct backflow prevention device installed, and keep it in good working order.
  • Use an accredited backflow plumber to assess the hazard, and to test and register the device. Only backflow-accredited licensed plumbers can commission, test and register a containment device.
  • Test each testable device every year.
  • Make sure the results reach Sydney Water within 2 days of the test.

Sydney Water keeps a register of testable devices and reminds owners each year when testing is due. Outside Sydney Water's area, check with your local water utility.

GUIDE

Hazard ratings and devices

Hazard ratingWhat Sydney Water requires
Low20 mm and 25 mm meters have a backflow device built in. Larger meters need a non-testable containment device.
MediumA testable double check valve on drinking water connections. Fire services need a double check detector assembly.
HighA registered break tank, a reduced pressure zone device or a registered air gap.
UnknownTreated as high hazard.

Sydney Water treats alternative supplies such as stormwater or greywater, and construction work for more than a single standalone house, as high hazard (Sydney Water, plumbing).

GUIDE

Containment, zone and individual protection

  • Containment: at the property boundary, straight after the master water meter. Every connection to Sydney Water's mains must have containment.
  • Zone: at the connection to a section of the plumbing inside the building.
  • Individual: at the connection to a single fixture or appliance.

Zone and individual devices are not registered on Sydney Water's portal. Sydney Water directs questions about them to Building Commission NSW. Ask your plumber which of your devices are testable and when each is due.

Fire services.Sydney Water requires a double check detector assembly on all sprinkler and fire hydrant services. Older fire services without a device must be upgraded if they are moved, repaired, redeveloped or upgraded. Because fire services are often the building's testable device, coordinate the backflow test with your fire services contractor.

GUIDE

How to find out what your building has

  • Check your mail. Sydney Water keeps a register of installed testable containment devices and reminds owners each year when a test is due. If the reminders go to a previous strata manager or owner, update the contact details.
  • Look near the master meter. A containment device sits at the boundary or straight after the meter. Testable devices usually carry a tag or label from the last test.
  • Check the fire service. If the building has sprinklers or hydrants, look where the fire service leaves the main supply. Each fire connection needs its own testable assembly, so there may be more than one.
  • Ask about the tenancies. Food businesses are a common case: Sydney Water lists a backflow containment device at the boundary or directly after the meter among its requirements for them (Sydney Water: food businesses). Medical, dental and laundry equipment may need zone or individual protection inside.

If you are buying, leasing or taking over management of a building, ask for the hazard rating, the device list and the last test results before you sign. A missed test is cheap to fix; finding out from a Sydney Water notice is not.

GUIDE

How a backflow test runs

  1. Book: the test is booked before it falls due, at a time that suits the building.
  2. Shut off:a short shutdown of the supply through the device.
  3. Test: the accredited plumber checks each valve in the device with a test kit.
  4. Lodge: the results go to Sydney Water within 2 days, and you get a copy.
  5. Fix: if the device fails, it is repaired or replaced and tested again.

Keep each year's results with the building's compliance records.

GUIDE

If a device fails or a test is missed

A failed device is repaired or replaced, then tested again. If an installation does not meet the standards, Sydney Water sends a notice asking the owner to repair, maintain, test or replace the device. If the owner does not comply, Sydney Water can test the device and charge for it, restrict the water supply, disconnect the property, or recover its costs.

Watch out

Devices are sometimes damaged or bypassed during other work, such as a fit-out. Test after any work near the device, not just when the reminder arrives.

Ask your plumber

What hazard rating is our site, which devices do we have, which are testable, and when is each one due?

Proximity Plumbing is a Sydney Water registered backflow tester. If you are not sure what your building has, start with backflow testing.

DOWNLOAD

Annual strata plumbing compliance calendar

Free to download and print: Annual strata plumbing compliance calendar.

QUESTIONS

Questions

SERVICES

How we can help

SOURCES

Sources

Last updated 8 November 2026. General information, not legal advice.

COMMERCIAL & STRATA

Explore Commercial & Strata

KNOWLEDGE CENTRE

Need a hand with this?

Log a job, or start with a free health check of your building.

Planning ahead? Request our compliance pack, book a free building health check or invite us to your contractor panel.

Licensed NSW 285594C

24/7 priority response

Report and photos on every job

4.9 from 3,000+ Google reviews